Protocol Gateways
IPG32-D2T1S-D2
2-Port EtherNet/IP-to-Modbus RTU Gateway
Front view
Side view
Side view
Label view
Back view
Top view
Features and Benefits
Supports 2 x 10/100 Mbit/s EtherNet/IP (RJ45) interfaces
Millisecond-level protocol conversion time
Complies with standard EtherNet/IP and Modbus protocol specifications
Supports 1 x RS485 serial port
Graphical configuration, no programming required
Overview
The IPG32-D2T1S-D2 is an industrial-grade EtherNet/IP-to-Modbus RTU protocol converter that enables bidirectional data mapping between the two protocols. It supports RS485 serial port, DIN-Rail mounting, and provides stable connection to serial devices such as instruments and inverters, facilitating the integration of heterogeneous devices in industrial networks.
Technical Parameters
| Serial Port | |
|---|---|
| Modbus Specification | V1.1b3 |
| Modbus RTU Specification | V1.02 |
| RS485 Interface | 3-pin terminal block, software-selectable interface |
| Node Scale | Max. 32 Modbus RTU slave devices, max. 128 Modbus commands, max. 128 custom commands |
| RS485 Termination Resistor | DIP switch matched termination resistor (120Ω) |
| Supported Baud Rate | 1200 Bit/s, 2400 Bits/s, 4800 Bits/s, 9600 Bits/s, 19200 Bits/s, 38400 Bits/s, 57600 Bit/s, 115200 Bits/s |
| Modbus RTU Master/Slave | Master/Slave selectable |
| Parity Check | Supports odd, even, none parity options |
| Modbus RTU Function Codes | Function codes 01H, 02H, 03H, 04H, 05H, 06H, 0FH, 10H |
| Custom Protocol Communication Model | Request-response mode |
| Custom Protocol Basic Elements | Constant, variable, checksum |
| Custom Protocol Trigger | Supported, trigger address configurable |
| EtherNet/IP | |
| CIP & EIP Specification | Edition3.1&Edition1.24 |
| EDS | Supports |
| EtherNet/IP Interface | 2 x 100 Mbit/s Ethernet, 2 x RJ45 connectors |
| Max. Data Supported | 500 bytes IN + 500 bytes OUT |
| Switch | Integrated dual-port switch |
| Protocol Conversion Time | <2ms |
| Configuration Tool | |
| Configuration Interface | Ethernet interface |
| Project Management | Supports save and load |
| Language | Supports Chinese and English |
| Monitoring | Supports Modbus message monitoring |
| Modbus Point Table | Supports Modbus point table import and export |
| Interactive Mapping | Supports Modbus data and EtherNet/IP mapping configuration |
| Electrical Performance | |
| Power | 24VDC (-15% ~ +20%) 60mA@24VDC |
| Isolation | Triple isolation: Ethernet <=> Power <=> Ethernet |
| Protection | Reverse voltage / short circuit protection |
| Operating Temperature | -20°C ~ +70°C |
| Storage Temperature | -40°C ~ +85°C |
| Relative Humidity | 10% ~ 95% (non-condensing) |
| Mechanical | |
| Ingress Protection (IP) Rating | IP20 |
| Enclosure Material | Metal |
| Enclosure Dimensions | 34x 110 x 74 mm (W x H x D) |
| Weight | Approx. 330g |
| Mounting | DIN 35mm Rail Mounting |
| MTBF | MTBF greater than 500,000 hours |
Resources
Ordering Information
| Model | Description |
|---|---|
| IPG32-D2T1S-D | DIN-Rail EtherNet/IP-to-Modbus RTU Communication Gateway, 2 x 10/100 Mbit/s EtherNet/IP electrical ports to 1 x RS485 serial port, 24VDC power input |